SCLD69500NGT - 500Amp Circuit Breaker

The Siemens SCLD69500NGT circuit breaker is a 500-amp, three-pole SENTRON molded case circuit breaker (MCCB) for your electrical distribution equipment that requires a specific combination of current rating, frame dimensions, and electronic trip functions. Rated for 600V AC, this Siemens LD-frame breaker features 100kAIC interrupting capacity at 600V AC and 150kAIC at 480V AC. Its current-limiting breaking-capacity construction and standard 40°C breaker designation are part of the manufacturer's specifications, making them important details when evaluating the breaker for compatible commercial and industrial electrical systems.

Key Features and Benefits

  • 500-Amp Current Rating: Provides a manufacturer-defined 500A rating for compatible electrical distribution applications requiring this breaker capacity.
  • Three-Pole Configuration: Designed for three-pole electrical systems and equipment approved for this breaker arrangement.
  • 600V AC Voltage Rating: Supports applications within the specified voltage rating when all other equipment and system requirements are satisfied.
  • Siemens SENTRON Product Design: Identifies the breaker as part of the Siemens SENTRON molded case circuit breaker line.
  • LD-Frame Construction: Provides a defined frame configuration for evaluating physical compatibility with existing equipment.
  • SensiTrip Electronic Trip Unit: Incorporates Siemens electronic trip functions identified by the LSIG designation.
  • Long-Time Protection: Addresses sustained overcurrent conditions according to the applicable trip characteristics and settings.
  • Short-Time Protection: Includes a short-time trip function for qualifying overcurrent conditions, subject to the unit's available settings and application requirements.
  • Instantaneous Protection: Provides a trip response for qualifying high-current fault conditions without intentional delay.
  • Ground-Fault Protection: Includes the ground-fault trip function specified by Siemens for this LSIG configuration.
  • Included TA2J6500 Line and Load Lugs: Provide manufacturer-identified terminals on both sides of the breaker.

Technical Specifications

  • Manufacturer: Siemens
  • Product Line: SENTRON
  • Product Type: Molded Case Circuit Breaker (MCCB)
  • Catalog Number / MFN: SCLD69500NGT
  • Siemens Article Number: US2
  • UPC: 783643217676
  • Rated Current: 500 Amps
  • Number of Poles: 3
  • Rated Voltage: 600V AC
  • Interrupting Capacity at 600V AC: 100kAIC
  • Interrupting Capacity at 480V AC: 150kAIC
  • Frame Type: LD Frame
  • Trip Unit Type: Electronic Trip Unit (ETU)
  • Electronic Trip System: Siemens SensiTrip
  • Trip Function Designation: LSIG
  • Long-Time Protection (L): Included
  • Short-Time Protection (S): Included
  • Instantaneous Protection (I): Included
  • Ground-Fault Protection (G): Included
  • Standard Breaker Temperature Designation: 40°C
  • Breaking-Capacity Construction: Current-limiting
  • Line-Side Lugs: TA2J6500
  • Load-Side Lugs: TA2J6500
  • Copper Conductor Range: 3/0 AWG–500 kcmil
  • Aluminum Conductor Range: 4/0 AWG–500 kcmil
  • Width: 7.5 inches
  • Height: 17.86 inches
  • Depth: 4 inches
  • Overall Dimensions (W × H × D): 7.5 × 17.86 × 4 inches
  • Net Weight: 34.00 lb
  • Manufacturer-Stated Standards: Meets UL 489 / IEC 60947-2
  • Country of Origin: Mexico
  • Commodity Code: 8536200020
  • Export Classification: ECCN EAR99 / AL N
  • Siemens Product Group: 3741
  • Siemens Catalog ID: LV10.1
  • Siemens Group Code: P360

Material Compliance and Certifications

The Siemens SCLD69500NGT includes manufacturer-stated standards and environmental information that can help electrical professionals review documentation requirements for an existing installation.

  • UL 489: Siemens states that the SCLD69500NGT meets UL 489 requirements for molded case circuit breakers.
  • IEC 60947-2: Siemens also identifies IEC 60947-2 as a standard this model meets.
  • RoHS Substance Restrictions: Siemens reports compliance with the applicable substance restrictions under the RoHS directive since March 30, 2009.
  • REACH Article 33: Siemens references REACH Article 33 duty-to-inform information based on the current candidate list.
  • WEEE (2012/19/EU) Take-Back Obligations: Siemens identifies this field as No.

Where It Works Best

  • Compatible Legacy Siemens Switchboards
  • 500A Electrical Distribution Circuits
  • 480V AC Distribution Systems
  • 600V AC Distribution Systems
  • Industrial Electrical Equipment Maintenance
  • Commercial Power Distribution Equipment
  • LSIG Electronic Trip Applications
  • Ground-Fault Protection Applications
  • Existing LD-Frame Installations
  • Copper-Conductor Installations
  • Aluminum-Conductor Installations

Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.