SQUARE D

MJA36350 - 350 Amp Circuit Breaker

MJA36350 - 350 Amp Circuit Breaker

Regular price $0.00 USD
Regular price Sale price $0.00 USD
Sale Sold out
Shipping calculated at checkout.
Condition

MJA36350 - 350 Amp Circuit Breaker

When matching the MJA36350 to your existing electrical distribution equipment, the useful details go well beyond the 350 amp rating. This 3-pole circuit breaker carries a 600VAC rated operational voltage, uses an ET 1.0 basic electronic trip unit, and has an I-Line connection on the line side with mechanical lugs on the load side. For buyers replacing a breaker in compatible existing or legacy equipment, these specifications provide meaningful checkpoints to confirm form, fit, and function rather than relying on the catalog number alone.

Key Features and Benefits

  • 350 Amp, 3-Pole Configuration: Clearly defined electrical configuration helps narrow the fit check when replacing equipment in an existing distribution system.
  • 600VAC Rated Operational Voltage: Rated for operation up to 600VAC at 50/60Hz under UL 489.
  • ET 1.0 Electronic Trip Unit: Uses the specified basic electronic ET 1.0 trip technology rather than a thermal-magnetic configuration.
  • I-Line Configuration: The line side uses an I-Line connection, while the load side uses mechanical lugs. This connection arrangement is an important compatibility detail.
  • 80% Continuous Current Rating: The MJA36350 carries the manufacturer's stated 80% continuous current rating.
  • Push-to-Trip Function: An integral push-to-trip button lets you manually trip the breaker.
  • Known Conductor Range: The specified load-side connection accommodates 3 x 3/0 AWG through 3 x 500 kcmil aluminum/copper conductors.

Technical Specifications

  • Catalog Number: MJA36350
  • Product Type: Circuit Breaker
  • Rated Current: 350A
  • Number of Poles: 3
  • Rated Operational Voltage: 600VAC, 50/60Hz, UL 489
  • Network Frequency: 50/60Hz
  • Trip Unit: ET 1.0
  • Trip Unit Technology: Basic Electronic
  • Continuous Current Rating: 80%
  • Phase Connection: ABC
  • UL 489 AIR: 100kA @ 240VAC; 65kA @ 480VAC; 25kA @ 600VAC
  • IEC 60947-2 Icu: 65kA @ 240VAC; 50kA @ 380/415VAC
  • IEC 60947-2 Ics: 35kA @ 240VAC; 25kA @ 380/415VAC
  • Rated Impulse Withstand Voltage (Uimp): 8kV
  • Line-Side Connection: I-Line Connection
  • Load-Side Connection: Lugs
  • Circuit Breaker Application: HACR Rated
  • Height: 12.86 in (326.64 mm)
  • Width: 8.27 in (210.06 mm)
  • Depth: 8.05 in (204.47 mm)
  • Net Weight: 29 lb (13.2 kg)

Material Compliance and Certifications

The MJA36350 carries documented UL, CSA, and NOM product certifications and is CE-marked. Manufacturer specifications also list UL, CSA, NEMA, NOM-003-SCFI-2000, and IEC 60947-2 as applicable standards. The enclosure protection designation is IP40, with Pollution Degree 3 per IEC 60947-1. It is also identified as HACR rated.

Where It Works Best

The MJA36350 350 amp circuit breaker suits compatible electrical distribution equipment requiring a 3-pole, 600VAC, I-Line breaker with an ET 1.0 electronic trip unit and an 80% continuous current rating. For legacy replacement work, the I-Line's line-side connection, load-side lugs, physical dimensions, conductor range, trip characteristics, and interrupting ratings make it important to check the complete specification.


Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.

Square D® is a registered trademark of Schneider Electric. Products sold are surplus, used, or refurbished and are NOT supplied by Schneider Electric or its affiliates.

View full details