Skip to product information
1 of 1

SIEMENS

JXD22B200 - 200Amp Circuit Breaker

JXD22B200 - 200Amp Circuit Breaker

Regular price $0.00 USD
Regular price Sale price $0.00 USD
Sale Sold out
Shipping calculated at checkout.
Condition

JXD22B200 - 200Amp Circuit Breaker

The JXD22B200 has a fairly specific set of details to check when you're replacing a breaker already in service. It's a 200A, two-pole molded case circuit breaker, identified as Type JXD2-A, with a non-interchangeable trip unit. The JXD22B200 is built to last, but the main consideration with any replacement is getting the form, fit, and electrical ratings right for the equipment already in place.

Key Features and Benefits

  • 200A, two-pole configuration for equipment requiring these exact electrical characteristics.
  • Type JXD2-A identification helps narrow down compatibility with an existing installation.
  • Uses a non-interchangeable trip unit.
  • Load-side lugs are included.
  • Well suited to replacement work where the existing system calls for the same ratings and configuration.

Technical Specifications

  • Part Number: JXD22B200
  • Product Type: Molded Case Circuit Breaker
  • Type: JXD2-A
  • Amperage: 200A
  • Poles: 2
  • Trip Unit: Non-Interchangeable
  • AIC Rating: 65 kA at 240VAC
  • DC Interrupting Rating: 30 kA at 250VDC for two-pole applications
  • Load-Side Lugs: Included
  • Width: 7.50 in.
  • Height / Length: 11.00 in.
  • Depth: 4.00 in.
  • Overall Dimensions: 7.50 in. W × 11.00 in. L × 4.00 in. D
  • Approximate Ship Weight: 18.00 lb

Material Compliance and Certifications

The supplied specifications do not list UL, CSA, IEC, RoHS, REACH, or other certification or material-compliance information for the JXD22B200. Those approvals should not be assumed. If a particular standard is required for the installation, confirm it using the applicable product documentation before putting the breaker into service.

Where It Works Best

The JXD22B200 is a practical choice for compatible existing and legacy electrical equipment that already calls for a 200A, two-pole JXD2-A molded case circuit breaker. It's particularly important to match the interrupting ratings, physical dimensions, trip-unit arrangement, and load-side lug configuration—not simply the 200A rating.


Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.

Siemens®, I-T-E®, and Murray® are registered trademarks of Siemens AG. Products sold are surplus, used, or refurbished and are NOT supplied by Siemens AG or its affiliates.

View full details