When you're replacing a fuse, matching the 15A rating is only part of the job. The JTD015 is a 15-amp Class J time-delay fuse with industrial cartridge construction and maximum ratings of 600VAC and 300VDC. The JTD015 mounts in a compatible fuse block, clip, or holder; the LFPSJ30 Series is the specified holder family. Bottom line: if your equipment calls for a JTD015, compare the full set of electrical and physical requirements—not just the "15A" rating printed on the fuse.

Key Features and Benefits

  • 15A continuous current rating
  • Class J fuse
  • Time-delay operation for equipment requiring this specific opening characteristic
  • Rated for a maximum of 600VAC
  • Rated for a maximum of 300VDC
  • Industrial cartridge configuration
  • Part of the JTD Series
  • POWR-PRO Fuse family style
  • Non-indicating design
  • Installs using a compatible fuse block, clip, or holder
  • LFPSJ30 Series is the specified holder family

Technical Specifications

  • Catalog Number: JTD015
  • Series: JTD
  • Fuse Class: Class J
  • Continuous Current Rating: 15A
  • Opening: Slo-Blo / Time Lag (T) / Time Delay
  • Maximum AC Voltage: 600VAC
  • Maximum DC Voltage: 300VDC
  • AC Interrupting Value 1: 200,000A at 600VAC
  • AC Interrupting Value 2: 300,000A at 600VAC
  • DC Interrupting Rating: 20,000A at 300VDC
  • Size: Industrial Cartridge
  • Family Style: POWR-PRO Fuse
  • Indicating: No
  • Mounting Method: Fuse Block / Clip / Holder
  • Specified Holder: LFPSJ30 Series

Material Compliance and Certifications

The supplied information confirms the JTD015's Class J classification, electrical ratings, time-delay opening characteristic, industrial cartridge construction, mounting method, and other specifications listed above.

Where It Works Best

The JTD015 is a practical match for electrical equipment specifically designed to use a 15A Class J time-delay fuse with the corresponding electrical and physical requirements. For an AC application, confirm the equipment requirements against the 600VAC maximum rating and the applicable AC interrupting value. For DC use, the supplied data specifies a maximum of 300VDC with a 20 kA interrupting rating at 300VDC.


Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.

Littelfuse® is a registered trademark of Littelfuse, Inc. Products sold are surplus, used, or refurbished and are NOT supplied by Littelfuse, Inc. or its affiliates.