SIEMENS
HLD63B250L - 250Amp Circuit Breaker
HLD63B250L - 250Amp Circuit Breaker
Couldn't load pickup availability
HLD63B250L - 250Amp Circuit Breaker
The Siemens HLD63B250L is a 250-amp, 3-pole molded case circuit breaker in the SENTRON HLD6 family. Built around the LD frame, it uses a thermal-magnetic trip unit and is rated for your applications up to 600 VAC. Its interrupting capacity is 35 kAIC at 600V and 65 kAIC at 480V. This is a standard 40°C breaker supplied with TA2J6500 lugs on both the line and load sides, so the termination setup is already clearly defined. The lugs accept copper conductors from 3/0 AWG through 500 kcmil and aluminum conductors from 4/0 AWG through 500 kcmil.
Key Features and Benefits
- 250A, 3-pole breaker designed for compatible low-voltage distribution equipment.
- Rated for 600 VAC operation.
- Thermal-magnetic trip unit provides the protection characteristics specified for this breaker.
- Part of the HLD6 family and built on the LD frame.
- Standard 40°C breaker configuration.
- Includes TA2J6500 lugs on both line and load sides.
- Handles a broad conductor range: 3/0 AWG–500 kcmil copper and 4/0 AWG–500 kcmil aluminum.
- Meets UL 489 and IEC 60947-2 standards.
Technical Specifications
-
Manufacturer: Siemens
-
Catalog Number / MFN: HLD63B250L
-
Article Number: US2\:HLD63B250L
-
Breaker Type: Molded Case Circuit Breaker
-
Product Family: HLD6
-
Frame: LD
-
Trip Unit: Thermal-Magnetic
-
Amp Rating: 250A
-
Poles: 3
-
Voltage Rating: 600 VAC
-
Interrupting Rating at 600V: 35 kAIC
-
Interrupting Rating at 480V: 65 kAIC
-
Temperature Configuration: Standard 40°C
-
Line-Side Lugs: TA2J6500
-
Load-Side Lugs: TA2J6500
-
Copper Wire Range: 3/0 AWG–500 kcmil
-
Aluminum Wire Range: 4/0 AWG–500 kcmil
-
Dimensions (W × H × D): 7.5 × 11 × 4 in.
-
Net Weight: 19.533 lb
-
UPC: 783643434509
-
Country of Origin: Mexico
Material Compliance and Certifications
The HLD63B250L meets UL 489 and IEC 60947-2 standards, two important specifications to consider when confirming a circuit breaker for a particular electrical system.
The manufacturer's product data also provides REACH Article 33 information. RoHS substance-restriction compliance information and the SCIP number are listed as not available. If either is required for a particular project or facility, it should be confirmed during the project's compliance review.
Where It Works Best
The HLD63B250L makes the most sense in electrical distribution applications that specifically call for a 250A, 3-pole LD-frame breaker with a thermal-magnetic trip unit and 600 VAC rating. It's also well suited to maintenance and replacement work involving equipment designed around this particular breaker configuration.
And that's where checking the details pays off. A breaker isn't a match simply because the amperage looks right. When replacing an existing unit, compare the catalog number, frame, pole count, voltage, interrupting rating, trip type, dimensions, lug configuration, conductor material, and allowable wire sizes with the equipment requirements.
Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.
Siemens®, I-T-E®, and Murray® are registered trademarks of Siemens AG. Products sold are surplus, used, or refurbished and are NOT supplied by Siemens AG or its affiliates.
Share