Littelfuse
FLSR045-ID - 45Amp Fuse
FLSR045-ID - 45Amp Fuse
Couldn't load pickup availability
FLSR045-ID - 45Amp Fuse
When your circuit needs 45-amp Class RK5 protection but must also handle the normal inrush current associated with motors, transformers, and other inductive loads, the FLSR045-ID is designed for the job. This dual-element, time-delay cartridge fuse carries a 45A continuous current rating and is rated for use up to 600VAC or 300VDC. With its combination of Class RK5 protection, high interrupting capability, and time-delay performance, it’s a useful choice for demanding industrial and commercial electrical applications where reliable circuit protection and easier maintenance both matter.
Key Features and Benefits
- 45A continuous rating for circuits requiring 45-amp overcurrent protection.
- Class RK5, dual-element design combines time-delay performance with short-circuit protection.
- 600 VAC and 300 VDC maximum voltage ratings provide flexibility for compatible AC and DC applications.
- Time-delay operation helps accommodate temporary startup and inrush currents associated with motors, transformers, and similar loads.
- The built-in indication makes an open fuse easier to identify during inspection and troubleshooting.
- Industrial cartridge construction is designed for use with the appropriate fuse block, clip, or holder.
- Compatible with the LFR60060 Series PG holder.
Technical Specifications
-
Catalog Number: FLSR045-ID / FLSR045ID
-
Series: FLSR_ID
-
Fuse Type: Dual-Element Time-Delay Fuse
-
Fuse Class: Class RK5
-
Continuous Current Rating: 45A
-
Maximum AC Voltage: 600VAC
-
Maximum DC Voltage: 300VDC
-
Opening: Slo-Blo / Time Lag / Time Delay
-
AC Interrupt Amperage: 200,000A / 300,000A at 600VAC
-
DC Interrupting Rating: 20,000A at 300VDC
-
Indicating: Yes
-
Construction: Industrial Cartridge
-
Mounting: Fuse Block / Clip / Holder
-
PG Holder: LFR60060 Series
Material Compliance and Certifications
The FLSR045-ID is identified as a Class RK5 fuse. For installations where a particular certification, environmental standard, or material compliance declaration is required, the applicable documentation should be checked for the exact catalog number before installation.
Where It Works Best
The FLSR045-ID makes the most sense in electrical systems where temporary inrush current is normal but sustained overcurrent still needs dependable protection. Motors and transformers are good examples: they can draw substantially more current during startup than during normal operation, so the time-delay characteristic can help prevent unnecessary fuse openings during those brief startup conditions.
Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.
Littelfuse® is a registered trademark of Littelfuse, Inc. Products sold are surplus, used, or refurbished and are NOT supplied by Littelfuse, Inc. or its affiliates.