SQUARE D
FAL32080 - 80 Amp Circuit Breaker
FAL32080 - 80 Amp Circuit Breaker
Couldn't load pickup availability
FAL32080 - 80 Amp Circuit Breaker
Keeping your existing electrical system operating often comes down to finding a circuit breaker that matches the original design. While the amperage rating is important, so are the mounting method, pole configuration, and terminal style. The FAL32080 is an 80 Amp, 3-pole molded case circuit breaker designed for compatible FA Series electrical equipment using a unit-mount configuration. Its thermal-magnetic trip unit provides two layers of protection: the thermal element responds to sustained overload conditions, while the magnetic element reacts quickly to short circuits.
Key Features and Benefits
- 80 Amp current rating
- Three-pole design for three-phase electrical systems
- Thermal-magnetic trip unit provides overload and short-circuit protection
- Unit-mount construction for compatible FA Series panelboards and equipment
- Line and load lug connections
- AL100FA terminal configuration
- HACR rated for qualifying heating, ventilation, air conditioning, and refrigeration applications
- Built to last for continued service in existing electrical systems
- Helps maintain the original form, fit, and function of compatible equipment
- UL Listed and CSA certified
Technical Specifications
-
Catalog Number: FAL32080
-
Series: FA
-
Product Type: Molded Case Circuit Breaker
-
Current Rating: 80 Amps
-
Number of Poles: 3
-
Voltage Class: 240V
-
Trip Unit Technology: Thermal-Magnetic
-
Breaking Capacity Code: A
-
Mounting Mode: Unit Mount
-
Phase Connection: ABC
-
Electrical Connections:
- Line Lugs
- Load Lugs
-
Terminal Identifier: AL100FA
-
Magnetic Hold Current: 800A
-
Magnetic Tripping Current: 1450A
-
Application Rating: HACR
-
Dimensions:
- Height: 6.4 in. (162.6 mm)
- Width: 4.5 in. (114.3 mm)
- Depth: 4.13 in. (104.9 mm)
Material Compliance and Certifications
The FAL32080 is UL Listed and CSA certified, demonstrating compliance with recognized North American safety standards for molded case circuit breakers. Before replacing an existing breaker, confirm that the amperage rating, voltage class, pole configuration, mounting style, and terminal connections match the equipment in service to ensure proper compatibility. Installation should always be completed by qualified electrical personnel in accordance with the National Electrical Code (NEC) and all applicable local electrical codes.
Where It Works Best
- Commercial buildings
- Industrial facilities
- Manufacturing plants
- Distribution panels
- Three-phase branch circuits
- HVAC and refrigeration equipment requiring an HACR-rated circuit breaker
- Maintenance and replacement projects involving compatible FA Series equipment
Use of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer. CIRCUIT BREAKER SUPERSTORE® is an independent reseller and is not an authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do not apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.
Square D® is a registered trademark of Schneider Electric. Products sold are surplus, used, or refurbished and are NOT supplied by Schneider Electric or its affiliates.
Share