{"product_id":"3va5210-7ed31-0aa0","title":"3VA5210-7ED31-0AA0 - CFAS 100 Amp Circuit Breaker","description":"\u003cp\u003e\u003cstrong\u003e3VA5210-7ED31-0AA0 - CFAS 100 Amp Circuit Breaker\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eSome breakers are just spec-sheet fillers. This isn’t one of them. The Siemens 3VA5210-7ED31-0AA0 is built for situations where fault current isn’t small—and mistakes get expensive fast. You’re looking at a 100A, 3-pole breaker with a 100kA interrupting rating at 480V, which puts it in a category you typically use for serious commercial or industrial work. What most people like about this model? It keeps things simple. The thermal-magnetic trip unit (TM210) comes with fixed settings. No dialing things in, no second-guessing. Overload is locked at 100A, and short-circuit protection trips at 10x that. It does exactly what it’s supposed to do—nothing fancy, nothing unpredictable. Physically, it’s part of Siemens’ 3VA5 frame family (Frame 250), so it’s compact enough to work into tight panel layouts without becoming a problem. If you’ve worked in crowded gear before, you already know how much that matters. This is the kind of breaker you install and move on. It just sits there and does its job.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eKey Features and Benefits\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003e100kA interrupting rating @ 480V:\u003c\/strong\u003e handles high fault levels without hesitation\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e100A continuous rating:\u003c\/strong\u003e solid choice for mid-range distribution loads\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eThermal-magnetic trip (TM210):\u003c\/strong\u003e dependable, widely used protection style\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFixed protection settings:\u003c\/strong\u003e fewer variables, faster installs\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003e3-pole configuration:\u003c\/strong\u003e standard for three-phase systems\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompact Frame 250 design:\u003c\/strong\u003e easier fit in real-world panels\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eC-interrupting class:\u003c\/strong\u003e built for higher-demand protection scenarios\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003ePart Number:\u003c\/strong\u003e 3VA5210-7ED31-0AA0\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeries:\u003c\/strong\u003e Siemens 3VA52\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePoles:\u003c\/strong\u003e 3\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAmps:\u003c\/strong\u003e 100A\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInterrupting Capacity:\u003c\/strong\u003e 100kA @ 480V\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTrip Unit:\u003c\/strong\u003e TM210 (Thermal Magnetic)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOverload (Ir):\u003c\/strong\u003e 100A, fixed\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShort-Circuit (Ii):\u003c\/strong\u003e 10 × In, fixed\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFrame:\u003c\/strong\u003e UL 250\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDimensions:\u003c\/strong\u003e\n\u003cul\u003e\n\u003cli\u003eHeight: 9.65 in\u003c\/li\u003e\n\u003cli\u003eWidth: 6.3 in\u003c\/li\u003e\n\u003cli\u003eDepth: 5.9 in\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eMaterial Compliance and Certifications\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eUL Listed for use in the U.S.\u003c\/li\u003e\n\u003cli\u003eBuilt to meet standard NEC applications\u003c\/li\u003e\n\u003cli\u003eDesigned for commercial and industrial environments\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eWhere It Works Best\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eCommercial buildings with higher available fault current\u003c\/li\u003e\n\u003cli\u003eIndustrial panels and machinery feeds\u003c\/li\u003e\n\u003cli\u003eManufacturing facilities\u003c\/li\u003e\n\u003cli\u003eOEM equipment builds\u003c\/li\u003e\n\u003cli\u003eRetrofit jobs where space and interrupting capacity both matter\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cdiv\u003e\n\u003cbr\u003e\n\u003cdiv\u003e\n\u003cblockquote\u003e\n\u003cp style=\"font-size: 12px;\"\u003e\u003cem\u003eUse of Original Equipment Manufacturer (OEM) trademarks, names, and logos is for informational and identification purposes only. This does not imply any affiliation, sponsorship, endorsement, or approval by the original equipment manufacturer.\u003cstrong\u003e CIRCUIT BREAKER SUPERSTORE®\u003c\/strong\u003e is an independent reseller and is \u003cstrong\u003enot \u003c\/strong\u003ean authorized distributor, affiliate, or representative of any manufacturer. Manufacturer warranties do \u003cstrong\u003enot\u003c\/strong\u003e apply unless expressly stated. All trademarks and registered trademarks are the property of their respective owners.\u003c\/em\u003e\u003c\/p\u003e\n\u003cp style=\"font-size: 12px;\"\u003e\u003cem\u003eSiemens®, I-T-E®, and Murray® are registered trademarks of Siemens AG. Products sold are surplus, used, or refurbished and are \u003cstrong\u003eNOT \u003c\/strong\u003esupplied by Siemens AG or its affiliates.\u003c\/em\u003e\u003c\/p\u003e\n\u003c\/blockquote\u003e\n\u003c\/div\u003e\n\u003c\/div\u003e","brand":"SIEMENS","offers":[{"title":"New","offer_id":51696279912747,"sku":"3VA5210-7ED31-0AA0","price":1500.0,"currency_code":"USD","in_stock":false}],"url":"https:\/\/store.circuitbreakersuperstore.com\/products\/3va5210-7ed31-0aa0","provider":"CIRCUIT BREAKER SUPERSTORE®","version":"1.0","type":"link"}